High-Quality AHF Harmonic Filter from China Suppliers and Factory for Power Quality Improvement
AHF is suitable for industrial high-capacity loads, such as rectifiers, frequency converters, large UPS, arc furnaces, intermediate frequency furnaces, three-phase chargers, and other three-phase load scenarios. Suitable for single-phase nonlinear loads in commercial buildings, such as energy-saving lamps, computers, UPS, elevators, variable frequency air conditioners, etc., which generate third harmonic and heat up the N-line.
Technical Indicators
| Item | 400V | 660V | |||
| Current rating | 50A | 100A | 135A | 50A | 100A |
| Voltage level | 380V, 440V, 480V | 600V, 660V, 690V | |||
| Voltage range | -20%~+15% | ||||
| Frequency | 50/60Hz±5% | ||||
| Phases | 3 phase 3 wire, 3 phase 4 wire | ||||
| Response time | ≤10us | ||||
| Parallel operation | Unlimited, Max 6 modules for one SAM controller | ||||
| Overload capability | 110%, 1 minute | ||||
| Efficiency | ≥97.5% | ||||
| CT location | Grid side or Load side | ||||
| Function | Harmonics, reactive power, unbalance compensation | ||||
| Harmonics | Up to 50th order | ||||
| Communication | Modbus, TCP/IP, IEC61850, others upon request | ||||
Products Advantage
Thermal design and structural optimization based on precise models.
Miniaturization, occupying less space.
Compensation for specified harmonic frequencies, adjustable inductive and capacitive reactive power compensation system, automatic detection of unbalanced loads, suppression of system resonance, and full function monitoring system.
Increased operational efficiency by avoiding unplanned stops.
Lower losses in the transformer.
Prolonged equipment lifetime.
Standard compliance.
Frequently Asked Questions
Q: What applications are suitable for Active Harmonic Filters (AHF)?
AHF is highly suitable for industrial high-capacity loads (such as rectifiers, frequency converters, large UPS, arc furnaces, intermediate frequency furnaces, and three-phase chargers) as well as commercial building single-phase non-linear loads (such as energy-saving lamps, computers, elevators, and variable frequency air conditioners).
Q: What is the response time and efficiency of this AHF?
The system features an ultra-fast response time of ≤10us and operates with a high efficiency of ≥97.5%.
Q: How many AHF modules can be operated in parallel?
Parallel operation is unlimited, allowing up to 6 modules to be controlled by a single SAM controller.
Q: What harmonic orders can the AHF compensate for?
The system can mitigate harmonics up to the 50th order, providing comprehensive power quality control including harmonic, reactive power, and unbalance compensation.
Q: What communication protocols does the AHF support?
It supports Modbus, TCP/IP, and IEC61850. Other communication protocols can also be provided upon request.