LOPS Lightning Monitoring and Overvoltage Protection Suppressor

 

    Lightning Monitoring and Overvoltage Protection Suppressor

    1.Protection,BlindSpots, and  Hazards

    (1) Frequent Overvoltage Problems, Insufficient Protection, Hidden Risks, and Serious Consequences

    Overvoltage events occur frequently in industrial power systems. Traditional protection methods cannot completely eliminate

    potential risks, which may lead to equipment damage and serious production  losses.

    (2) Insufficient Real-Time Monitoring Capability for Overvoltage Events

    Conventional transient waveform recording based on

    millisecond-level time resolution cannot accurately capture rapid

    changing transient overvoltage processes. Higher sampling

    frequency and nanosecond-level time resolution are required to

    Achieve full-process real-time sensing, waveform visualization, event identification, and intelligent control.

    (3) Existing Protection Devices Cannot Fundamentally Solve Power System Overvoltage Problems

    Existing solutions based on lightning arresters and combined

    Overvoltage protection devices cannot fundamentally address transient

    overvoltage issues occurring in power systems.

    (4) Lack of Effective Monitoring and Active Suppression Measures for

    Grounding Overvoltage

    Traditional systems lack effective monitoring and active suppression methods for grounding-related overvoltage.

    2.CurrentStatus of OvervoltageProtection

    Lightning Arrester Protection Parameters

    Lightning

    System Rated Voltage

    Arrester Rated

    Reference Voltage

    Residual Voltage Under

    Arrester Model

    (RMS) Arrester

    Voltage (RMS)

    at DC 1mA

    Impulse Current (Peak)

    HY5WS-10/30

    6kV

    7.6kV

    15kV

    30~35kV

    HY5WR-15/45

    10kV

    12kV

    23kV

    45~52kV

    HY5WZ-51/134

    35kV

    51kV

    73kV

    134~154kV

    Starting discharge voltage:Generally 2-3 times the system rated voltage.

    Residual    voltage:Generally    4-6    times     the    system     rated    voltage.

    Three-Phase Combined Overvoltage Protector Parameters

    Three-phase Combined

    Overvoltage Protector Model

    System Rated Voltage (RMS)

    Protector Rated Voltage (RMS)

    Allowable Operating Voltage Range (RMS)

    TBP-B7.6/150N

    6kV

    7.6kV

    12~17 kV

    TBP-B12/200N

    10 kV

    12kV

    20~30 kV

    TBP-B42/310N

    35 kV

    42kV

    65~90kV

    Starting discharge voltage:Generally around 2-3 times the system rated voltage.

    Residual    voltage:Generally     around     3    times     the    system     rated     voltage.

    lightning-monitoring-and-overv-1

     3.MainFunctions

    (1) Lightning   Monitoring  and  Surge  Waveform Recording  Function

    (2) Busbar Overvoltage Suppression Function

    (3) Grounding Overvoltage Suppression Function

    (4) Complete Compatibility with  Existing  Protection Systems

    Note:

    The device does not affect the existing protection configuration and is fully compatible with existing system protection schemes. No  modification  is required, and  it  can  be  integrated  with  PT  cabinets.

    4.KeyTechnologies

    (1) Overvoltage Monitoring and Waveform Recording
    Automatically  records  operation  times, operating  duration, bus voltage, and  other  parameters.
    Sampling frequency: 10 MHz
    For transient overvoltage events, the voltage waveform can be recorded and stored in real time.
    Waveform resolution:100ns

    (2)Patented   Two-Level   Voltage    Suppression   Technology
    Level1:High-energy absorption unit is directly connected to the system.Extremely fast response.No response time delay.

    Level 2:When the voltage exceeds the presetallowable value:The overvoltage limiting unit is activated.The bus voltage is rapidly imited below 1.8
    times the rated voltage.

    (3)Grounding Overvoltage Suppression
    Actively suppresses grounding reverse overvoltage.

    lightning-monitoring-and-overv-2

    5.Technical  Advantages

    (1)Nanosecond-Level  Transient Waveform Monitoring

    During transient overvoltage events,the system performs real-time monitoring of bus voltage and achieves nanosecond-level waveform recording, allowing transient voltage data to be captured and stored accurately.

    (2)Super-Strong Overvoltage Suppression  Capability

    Suppresses various types of overvoltage occurring on the busbar.

    Lower operating voltage(1.6 times rated voltage).

    Lower residual voltage(1.8 times rated voltage).

    Ultra-high energy absorption capability (megajoule level).

    Traditional  protection  devices  are  typically  limited  to  the  kilojoule  level, while   LOPS   provides   significantly   enhanced   energy   absorption   capability.

    (3) Full-Scenario Reliable Compatibility

    Fully compatible with existing protection configurations.

    No modification to the existing system protection scheme is required.

    (4) Low Power Consumption and No Explosion Risk

    Under normal operating conditions, the device remains  in standby  mode with extremely low  power consumption.

    During overvoltage events, there is no risk of explosion, ensuring  safe  and  reliable  operation.

    6. PerformanceComparison

    No.

    Key Technical Performance

    Lightning Arrester

    Combined Overvoltage Protector

    LOPS

    1

    Starting discharge voltage

    2-3 times the system rated voltage

    2-3 times the system rated voltage

    1.6 times the rated voltage

    2

    Residual Voltage

    4–6 times the system rated voltage

    around 3 times the system rated voltage

    1.8 times the rated voltage

     

    3

    Energy

    Withstand Capacity

    6kV

    75A/2ms;40kA/10μs;<15kJ

    400A/2ms;40kA/10μs;<15kJ

    1kA/2ms;600kA/10μs;≥0.8MJ

    10kV

    75A/2ms;40kA/10μs;<20kJ

    400A/2ms;40kA/10μs;<20kJ

    2kA/2ms;1MA/10μs;≥1.3MJ

    35kV

    400A/2ms;65kA/10μs;<60kJ

    400A/2ms;65kA/10μs;<60kJ

    10kA/2ms;2MA/10μs;≥4.6MJ

    4

    Safety Vulnerability

    Unknown operating status,prone to explosion

    Unknown operating status,prone to explosion

    Operating status controllable,no explosion risk

    5

    Response Time

    Nanosecond level

    Nanosecond level

    Nanosecond level

    6

    Leakage Current

    μA  level

    μA  level

    μA  level

    7

    Mitigation Targets

    Lightning surge,switching overvoltage

    Switching overvoltage,oscillation overvoltage

    All transient overvoltage events

    7.Performance   Specifications

    Main Parameters

    Parameter Requirements

    Protection Operating Voltage

    1.6 times of rated voltage

    Residual Voltage

    1.8 times of rated voltage

     

    Energy Withstand Capacity

    6kV

    1kA/2ms;600kA/10us;≥0.8MJ

    10kV

    2kA/2ms;1MA/10us;≥1.3MJ

    35kV

    10kA/2ms;2MA/10us;≥4.6MJ

    Response Time

    ns-level

    Leakage Current

    μA-level

    Mitigation Targets

    All types of transient overvoltages,including lightning,switching,and oscillatory overvoltages

    Grounding Overvoltage Suppression Function

    Max.blocking voltage:25kV(transient)

    Sampling frequency

    10MHz

    Sampling Interval

    100ns

    Waveform Recording Duration

    >30s

    Measurement Accuracy

    1%

     

     

     

    Human-Machine Interface

    CPU: Industrial-grade low-power dual-core 2.41 GHz processor

    Communication Interfaces: 1× RS-232/485, 2× RS232, 4× USB 2.0, 1× VGA, 1× Gigabit LAN

    Touchscreen: 10.1" high-brightness TFT LCD, 1280 × 800 resolution

    Memory & Storage: 4GB RAM, 64GB SSD

     

    Operating Environment

    Installation Location: Indoor application

    Temperature:-30℃~60℃

    Humidity: 0–90% RH, non-condensing

    8.CabinetDimensions

    lightning-monitoring-and-overv-3

    Enhanced PT Cabinet

    1.Brief Introduction

    The Enhanced PT Cabinet is an integrated solution combining  the LOPS with a conventional PT Cabinet. It can fullyreplace both conventional PT cabinet and standalone overvoltage suppression cabinet. lightning-monitoring-and-overv-9

    2.Main Functions

    Voltage Transformation and

    Measurement

    Provides accurate voltage transformation and measurement functions for medium-voltage systems.

    Electrical Isolation and Safety Protection

    Provides reliable electrical isolation between the primary high-voltage system and secondary measurement/control circuits.Ensures operator safety and equipment

    protection.

    Power Distribution Function

    Provides reliable auxiliary power supply and distribution functions for related protection and monitoring equipment.

    Resonance Suppression

    Primary and secondary resonance elimination devices are provided to achieve resonance suppression.

    Transient Overvoltage Suppression

    Advanced overvoltage suppression technology is employed to effectively limit transient overvoltage and keep the bus residual voltage below 1.8 times the rated voltage.

    Energy Absorption and Discharge Function

    With megajoule-level energy absorption capability, it utilizes flexible energy discharge technology and grounding overvoltage suppression technology to successfully prevent traditional surge arresters from being destroyed by grounding overvoltage backfeed.

    Typical Project References

    Case 1: A Energy Company in Guizhou— LOPS

    The company is a large-scale coal enterprise invested in and constructed by Guizhou Province, with multiple mining areas located in the region. Due to the    complex  geographical  conditions  and  frequent  lightning  activities  in  the  area, equipment  failures  caused  by  lightning  strikes  occurred  frequently, affecting normal  production operations. To  improve  power system safety  and  reliability, the company  installed the LOPS. The device effectively  reduces the  impact  of lightning-induced overvoltage on the power system and improves the safety of power supply for production equipment.

    lightning-monitoring-and-overv-4

    Case 2   A Mining Company in Yunnan — Enhanced PT Cabinet

    A 35kV substation in the mining area experienced multiple incidents caused by  lightning-induced  overvoltage  during  the  lightning  season, including:

    • Damage to cable terminalheads
    • Insulation support failures
    • Otherpowerequipment failures

     

    These   incidents    seriously   affected    production   operations.

    Based on the original PT cabinet system, the company carried out a retrofit and upgraded it to an Enhanced PT Cabinet integrating LOPS technology.    After the upgrade:

    • The    existing    protection    configuration    remained     unchanged.
    • The   new   system   achieved   seamless   compatibility   with   the   originalprotectionscheme.
    • Noadditional  modificationto the  existing  system was  required.

    The  retrofit  significantly  improved  the  power  system's  transient  overvoltage protection capability and operational reliability.

    lightning-monitoring-and-overv-5

    Case 3: A Non-Ferrous Metal Smelting Company in Liaoning— LOPS

    The company is a large non-ferrous metal smelting enterprise, mainly engaged in:

    • Zincproduction
    • Copperprocessing
    • Aluminumsmeltingand related operations

    During operation, the power supply system was frequently affected by overvoltage disturbances, causing unplanned production shutdowns and affecting production continuity.

    To improve system reliability, the customer installed the LOPS.

    The solution provides:

    • Real-timemonitoringof transient overvoltage events
    • Activeovervoltagesuppression
    • Improved  protection  for  critical  production  equipment

    It ensures continuous, safe, and stable operation of the production line.