LOPS Lightning Monitoring and Overvoltage Protection Suppressor
Lightning Monitoring and Overvoltage Protection Suppressor
1.Protection,BlindSpots, and Hazards
(1) Frequent Overvoltage Problems, Insufficient Protection, Hidden Risks, and Serious Consequences
Overvoltage events occur frequently in industrial power systems. Traditional protection methods cannot completely eliminate
potential risks, which may lead to equipment damage and serious production losses.
(2) Insufficient Real-Time Monitoring Capability for Overvoltage Events
Conventional transient waveform recording based on
millisecond-level time resolution cannot accurately capture rapid
changing transient overvoltage processes. Higher sampling
frequency and nanosecond-level time resolution are required to
Achieve full-process real-time sensing, waveform visualization, event identification, and intelligent control.
(3) Existing Protection Devices Cannot Fundamentally Solve Power System Overvoltage Problems
Existing solutions based on lightning arresters and combined
Overvoltage protection devices cannot fundamentally address transient
overvoltage issues occurring in power systems.
(4) Lack of Effective Monitoring and Active Suppression Measures for
Grounding Overvoltage
Traditional systems lack effective monitoring and active suppression methods for grounding-related overvoltage.
2.CurrentStatus of OvervoltageProtection
Lightning Arrester Protection Parameters
|
Lightning |
System Rated Voltage |
Arrester Rated |
Reference Voltage |
Residual Voltage Under |
|
Arrester Model |
(RMS) Arrester |
Voltage (RMS) |
at DC 1mA |
Impulse Current (Peak) |
|
HY5WS-10/30 |
6kV |
7.6kV |
15kV |
30~35kV |
|
HY5WR-15/45 |
10kV |
12kV |
23kV |
45~52kV |
|
HY5WZ-51/134 |
35kV |
51kV |
73kV |
134~154kV |
Starting discharge voltage:Generally 2-3 times the system rated voltage.
Residual voltage:Generally 4-6 times the system rated voltage.
Three-Phase Combined Overvoltage Protector Parameters
|
Three-phase Combined Overvoltage Protector Model |
System Rated Voltage (RMS) |
Protector Rated Voltage (RMS) |
Allowable Operating Voltage Range (RMS) |
|
TBP-B7.6/150N |
6kV |
7.6kV |
12~17 kV |
|
TBP-B12/200N |
10 kV |
12kV |
20~30 kV |
|
TBP-B42/310N |
35 kV |
42kV |
65~90kV |
Starting discharge voltage:Generally around 2-3 times the system rated voltage.
Residual voltage:Generally around 3 times the system rated voltage.

3.MainFunctions
(1) Lightning Monitoring and Surge Waveform Recording Function
(2) Busbar Overvoltage Suppression Function
(3) Grounding Overvoltage Suppression Function
(4) Complete Compatibility with Existing Protection Systems
Note:
The device does not affect the existing protection configuration and is fully compatible with existing system protection schemes. No modification is required, and it can be integrated with PT cabinets.
4.KeyTechnologies
(1) Overvoltage Monitoring and Waveform Recording
Automatically records operation times, operating duration, bus voltage, and other parameters.
Sampling frequency: 10 MHz
For transient overvoltage events, the voltage waveform can be recorded and stored in real time.
Waveform resolution:100ns
(2)Patented Two-Level Voltage Suppression Technology
Level1:High-energy absorption unit is directly connected to the system.Extremely fast response.No response time delay.
Level 2:When the voltage exceeds the presetallowable value:The overvoltage limiting unit is activated.The bus voltage is rapidly imited below 1.8
times the rated voltage.
(3)Grounding Overvoltage Suppression
Actively suppresses grounding reverse overvoltage.

5.Technical Advantages
(1)Nanosecond-Level Transient Waveform Monitoring
During transient overvoltage events,the system performs real-time monitoring of bus voltage and achieves nanosecond-level waveform recording, allowing transient voltage data to be captured and stored accurately.
(2)Super-Strong Overvoltage Suppression Capability
Suppresses various types of overvoltage occurring on the busbar.
Lower operating voltage(1.6 times rated voltage).
Lower residual voltage(1.8 times rated voltage).
Ultra-high energy absorption capability (megajoule level).
Traditional protection devices are typically limited to the kilojoule level, while LOPS provides significantly enhanced energy absorption capability.
(3) Full-Scenario Reliable Compatibility
Fully compatible with existing protection configurations.
No modification to the existing system protection scheme is required.
(4) Low Power Consumption and No Explosion Risk
Under normal operating conditions, the device remains in standby mode with extremely low power consumption.
During overvoltage events, there is no risk of explosion, ensuring safe and reliable operation.
6. PerformanceComparison
|
No. |
Key Technical Performance |
Lightning Arrester |
Combined Overvoltage Protector |
LOPS |
|
|
1 |
Starting discharge voltage |
2-3 times the system rated voltage |
2-3 times the system rated voltage |
1.6 times the rated voltage |
|
|
2 |
Residual Voltage |
4–6 times the system rated voltage |
around 3 times the system rated voltage |
1.8 times the rated voltage |
|
|
3 |
Energy Withstand Capacity |
6kV |
75A/2ms;40kA/10μs;<15kJ |
400A/2ms;40kA/10μs;<15kJ |
1kA/2ms;600kA/10μs;≥0.8MJ |
|
10kV |
75A/2ms;40kA/10μs;<20kJ |
400A/2ms;40kA/10μs;<20kJ |
2kA/2ms;1MA/10μs;≥1.3MJ |
||
|
35kV |
400A/2ms;65kA/10μs;<60kJ |
400A/2ms;65kA/10μs;<60kJ |
10kA/2ms;2MA/10μs;≥4.6MJ |
||
|
4 |
Safety Vulnerability |
Unknown operating status,prone to explosion |
Unknown operating status,prone to explosion |
Operating status controllable,no explosion risk |
|
|
5 |
Response Time |
Nanosecond level |
Nanosecond level |
Nanosecond level |
|
|
6 |
Leakage Current |
μA level |
μA level |
μA level |
|
|
7 |
Mitigation Targets |
Lightning surge,switching overvoltage |
Switching overvoltage,oscillation overvoltage |
All transient overvoltage events |
|
7.Performance Specifications
|
Main Parameters |
Parameter Requirements |
|
|
Protection Operating Voltage |
1.6 times of rated voltage |
|
|
Residual Voltage |
1.8 times of rated voltage |
|
|
Energy Withstand Capacity |
6kV |
1kA/2ms;600kA/10us;≥0.8MJ |
|
10kV |
2kA/2ms;1MA/10us;≥1.3MJ |
|
|
35kV |
10kA/2ms;2MA/10us;≥4.6MJ |
|
|
Response Time |
ns-level |
|
|
Leakage Current |
μA-level |
|
|
Mitigation Targets |
All types of transient overvoltages,including lightning,switching,and oscillatory overvoltages |
|
|
Grounding Overvoltage Suppression Function |
Max.blocking voltage:25kV(transient) |
|
|
Sampling frequency |
10MHz |
|
|
Sampling Interval |
100ns |
|
|
Waveform Recording Duration |
>30s |
|
|
Measurement Accuracy |
1% |
|
|
Human-Machine Interface |
CPU: Industrial-grade low-power dual-core 2.41 GHz processor |
|
|
Communication Interfaces: 1× RS-232/485, 2× RS232, 4× USB 2.0, 1× VGA, 1× Gigabit LAN |
||
|
Touchscreen: 10.1" high-brightness TFT LCD, 1280 × 800 resolution |
||
|
Memory & Storage: 4GB RAM, 64GB SSD |
||
|
Operating Environment |
Installation Location: Indoor application |
|
|
Temperature:-30℃~60℃ |
||
|
Humidity: 0–90% RH, non-condensing |
||
8.CabinetDimensions

Enhanced PT Cabinet
1.Brief Introduction
| The Enhanced PT Cabinet is an integrated solution combining the LOPS with a conventional PT Cabinet. It can fullyreplace both conventional PT cabinet and standalone overvoltage suppression cabinet. | ![]() |
2.Main Functions
|
Voltage Transformation and Measurement |
Provides accurate voltage transformation and measurement functions for medium-voltage systems. |
|
Electrical Isolation and Safety Protection |
Provides reliable electrical isolation between the primary high-voltage system and secondary measurement/control circuits.Ensures operator safety and equipment protection. |
|
Power Distribution Function |
Provides reliable auxiliary power supply and distribution functions for related protection and monitoring equipment. |
|
Resonance Suppression |
Primary and secondary resonance elimination devices are provided to achieve resonance suppression. |
|
Transient Overvoltage Suppression |
Advanced overvoltage suppression technology is employed to effectively limit transient overvoltage and keep the bus residual voltage below 1.8 times the rated voltage. |
|
Energy Absorption and Discharge Function |
With megajoule-level energy absorption capability, it utilizes flexible energy discharge technology and grounding overvoltage suppression technology to successfully prevent traditional surge arresters from being destroyed by grounding overvoltage backfeed. |
Typical Project References
Case 1: A Energy Company in Guizhou— LOPS
The company is a large-scale coal enterprise invested in and constructed by Guizhou Province, with multiple mining areas located in the region. Due to the complex geographical conditions and frequent lightning activities in the area, equipment failures caused by lightning strikes occurred frequently, affecting normal production operations. To improve power system safety and reliability, the company installed the LOPS. The device effectively reduces the impact of lightning-induced overvoltage on the power system and improves the safety of power supply for production equipment.

Case 2 A Mining Company in Yunnan — Enhanced PT Cabinet
A 35kV substation in the mining area experienced multiple incidents caused by lightning-induced overvoltage during the lightning season, including:
- Damage to cable terminalheads
- Insulation support failures
- Otherpowerequipment failures
These incidents seriously affected production operations.
Based on the original PT cabinet system, the company carried out a retrofit and upgraded it to an Enhanced PT Cabinet integrating LOPS technology. After the upgrade:
- The existing protection configuration remained unchanged.
- The new system achieved seamless compatibility with the originalprotectionscheme.
- Noadditional modificationto the existing system was required.
The retrofit significantly improved the power system's transient overvoltage protection capability and operational reliability.

Case 3: A Non-Ferrous Metal Smelting Company in Liaoning— LOPS
The company is a large non-ferrous metal smelting enterprise, mainly engaged in:
- Zincproduction
- Copperprocessing
- Aluminumsmeltingand related operations
During operation, the power supply system was frequently affected by overvoltage disturbances, causing unplanned production shutdowns and affecting production continuity.
To improve system reliability, the customer installed the LOPS.
The solution provides:
- Real-timemonitoringof transient overvoltage events
- Activeovervoltagesuppression
- Improved protection for critical production equipment
It ensures continuous, safe, and stable operation of the production line.
![]() |
![]() |
![]() |