LOPS Overvoltage Protection Device for MV Bus - High-Efficiency Solutions from China Suppliers and Factory
Functional Features
High Energy Nonlinear Resistor Chip Matching Technology
The nonlinear resistor adopts unique heat dissipation technology and a fully sealed process, with excellent heat dissipation and moisture prevention effects, stable working performance, long service life, safety, and reliability.
Overvoltage Peak Cutting Technology
When transient overvoltage occurs in the system and exceeds 1.2 times the rated peak voltage, the overvoltage peak interceptor immediately acts to cut off the high voltage wave head, ensuring safe operation of busbar load equipment.
Secondary Pressure Limiting Technology
After first-level voltage limiting activation, if bus voltage still exceeds the set allowable threshold, the LOPS equipment initiates an overvoltage chopper to rapidly clamp the bus voltage to 1.2 times or less.
Rapid Response Technology
Minimal action delay: the first level features zero-delay response, while the second level responds within 2 milliseconds. Delivers superior steep wave response, short nonlinear resistor conduction time, active protection, and high safety performance.
Overvoltage Recording Technology
The LOPS low-voltage bus overvoltage suppression equipment automatically records parameters including action counts, action duration, and bus voltage levels during events, providing comprehensive data for technical analysis.
Products Specification
| NO. | Spec | Arrestor | TBP | LOPS | |
|---|---|---|---|---|---|
| 1 | Action voltage | 2~3 times | 2~3 times | 1.25 times | |
| 2 | Residual voltage | 4~6 times | 3 times | 1.35 times | |
| 3 | Withstand energy | 6kV | 75A/2ms; 40kA/10μs; <15kJ | 400A/2ms; 40kA/10μs; <15kJ | 1kA/2ms; 600kA/10μs; ≥1MJ |
| 10kV | 75A/2ms; 40kA/10μs; <20kJ | 400A/2ms; 40kA/10μs; <20kJ | 2kA/2ms; 1MA/10μs; ≥2MJ | ||
| 35kV | 400A/2ms; 65kA/10μs; <60kJ | 400A/2ms; 65kA/10μs; <60kJ | 10kA/2ms; 2MA/10μs; ≥75MJ | ||
| 4 | Risk | Unknown status, explode | Unknown status, explode | Controllable operation status without explosion | |
| 5 | Response time | ≤50ns | ≤50ns | ≤50ns | |
| 6 | Leakage current | ≤1mA | ≤1mA | ≤1mA | |
| 7 | Effectiveness | Lightning overvoltage, switching overvoltage | Switching overvoltage, resonance overvoltage | All overvoltage | |