Leave Your Message
Products Categories
Featured Products

Multi-Function SAVS Recorder for Power Monitoring - China Suppliers & Factory for HV/LV Systems

The SAVS is an advanced multifunction recorder designed for comprehensive monitoring of power systems, ensuring high standards of system stability and power quality. As a reliable solution, it is suitable for both high voltage (HV) and low voltage (LV) bus applications. This cutting-edge device captures voltages and currents across three-phase lines with impressive 16-bit accuracy, utilizing standard instrumentation transformers. Additionally, the SAVS allows for real-time monitoring of protection relays and switchgear through auxiliary switch contacts. Trusted by numerous suppliers and factories across China, the SAVS stands out as an essential tool for efficient power management and system reliability

    products description

    The SAVS is a multi-function recorder that includes the features of many separate instruments for monitoring a power system. These include system stability, and power quality. SAVS can be used both on HV and LV bus. The voltages and currents on three phase lines are recorded via standard instrumentation transformers to 16-bit accuracy. The state of protection relays and switchgear can also be monitored via auxiliary switch contacts.
    SAVS For Sag Recording
    SAVS For Sag Recording
    SAVS For Sag Recording

    products specification

    Main functions descriptions features
    Sag start time Real time monitoring and recording 1s recording before sag
    Sag end time Real time monitoring and recording 30s recording after sag
    Sag duration time Real time monitoring and recording accurately identifying 1ms sag
    Sag drop depth Real time monitoring and recording Monitor, display residual voltage
    Sag drop rate Monitor, recording and record the rate of voltage drop Analyze, calculate sag drop rate
    Sag current change Real time monitoring and recording Monitor and display surge current
    Sag source identify Identifying the sag is from the power grid or a load short circuit Intelligent judgment of sag source
    Sag phase identify Discrimination is the sag of 1-phase, 2-phases, or 3-phase phase separation monitoring
    Statistics of sag No. Classify and count the number of sag Probability and statistical characteristics of sag
    Statistics of duration Count the duration of sag
    Statistics of depth Calculate the depth of sag
    Solution Recommendation Recommend a cost-effective solution for sag Assist customers in developing solutions
    data export exported to a USB flash drive or communicated to the backend Multiple protocols and interfaces
    Routine PQ monitoring V、I、power factor、THD、unbalance, etc. No need other PQ monitors

    products advantage

    No. items Main technical features
    1 Technical level (Six major upgrades)
    • High sampling frequency: 12kHz → 20kHz (sampling time: 83ms → 50ms)
    • More duration time recording: -0.2~+3s → -1~+30s (panoramic recording)
    • More duration time when power loss: 10s → 60s
    • Accurate time synchronization function: Beidou or GPS
    • Stronger analysis capabilities: real time analysis of voltage drop rate, type of sag, and reasons for sag
    • Solution Recommendation: Based on the analysis results of panoramic recording, recommend the most reasonable solution
    2 Process level (Four major upgrades)
    • Change the touch screen to 10 inches
    • Improve wiring methods: wiring terminals, wiring methods, etc
    • High strength anti vibration structural design
    • Artwork style full art design

    Frequently Asked Questions

    What is the SAVS and what are its primary applications?
    The SAVS is a multi-function recorder designed to monitor power system stability and power quality. It is suitable for use on both High Voltage (HV) and Low Voltage (LV) buses.
    What parameters does the SAVS track during a voltage sag event?
    The SAVS monitors and records sag start/end times, sag duration, drop depth, drop rate, current changes, sag source identification, and sag phase classification (1-phase, 2-phase, or 3-phase).
    How does the SAVS identify the source of a voltage sag?
    The system uses intelligent algorithms to determine whether the voltage sag originates from the power grid or is caused by a load short circuit.
    What are the key technical upgrades of the new SAVS model?
    Key upgrades include a higher sampling frequency of 20kHz, an extended panoramic recording time (-1 to +30s), a 60s power loss ride-through, and GPS/Beidou time synchronization.
    How can data be exported from the SAVS device?
    Data can be exported directly to a USB flash drive or transmitted to a backend system using multiple communication protocols and interfaces.
    Does the SAVS support routine power quality monitoring?
    Yes, it supports routine monitoring of voltage (V), current (I), power factor, Total Harmonic Distortion (THD), and unbalance, eliminating the need for additional power quality monitors.

    Leave Your Message