Leave Your Message
Products Categories
Featured Products

Multi-Function SAVS Recorder for Power System Monitoring | China Suppliers & Factory

Introducing the SAVS, a sophisticated multi-function recorder designed for comprehensive monitoring of power systems in China. As a reliable solution offered by top suppliers and factories, the SAVS combines the capabilities of several individual instruments to enhance system stability and power quality management. Suitable for both high voltage (HV) and low voltage (LV) bus systems, this advanced recorder captures voltages and currents across three-phase lines with exceptional 16-bit accuracy, utilizing standard instrumentation transformers. Additionally, it monitors the status of protection relays and switchgear through auxiliary switch contacts, ensuring optimal performance and safety. Discover the SAVS for unparalleled power system monitoring today

    Products Description

    The SAVS is a multi-function recorder that includes the features of many separate instruments for monitoring a power system. These include system stability, and power quality. SAVS can be used both on HV and LV bus. The voltages and currents on three phase lines are recorded via standard instrumentation transformers to 16-bit accuracy. The state of protection relays and switchgear can also be monitored via auxiliary switch contacts.
    SAVS For Sag Recording
    SAVS For Sag Recording
    SAVS For Sag Recording

    Products Specification

    Main functions Descriptions Features
    Sag start time Real time monitoring and recording 1s recording before sag
    Sag end time Real time monitoring and recording 30s recording after sag
    Sag duration time Real time monitoring and recording accurately identifying 1ms sag
    Sag drop depth Real time monitoring and recording Monitor, display residual voltage
    Sag drop rate Monitor, recording and record the rate of voltage drop Analyze, calculate sag drop rate
    Sag current change Real time monitoring and recording Monitor and display surge current
    Sag source identify Identifying the sag is from the power grid or a load short circuit Intelligent judgment of sag source
    Sag phase identify Discrimination is the sag of 1-phase, 2-phases, or 3-phase phase separation monitoring
    Statistics of sag No. Classify and count the number of sag Probability and statistical characteristics of sag
    Statistics of duration Count the duration of sag
    Statistics of depth Calculate the depth of sag
    Solution Recommendation Recommend a cost-effective solution for sag Assist customers in developing solutions
    data export exported to a USB flash drive or communicated to the backend Multiple protocols and interfaces
    Routine PQ monitoring V、I、power factor、THD、unbalance, etc. No need other PQ monitors

    Products Advantage

    No. Items Main Technical Features
    1 Technical level (Six major upgrades)
    • High sampling frequency: 12kHz → 20kHz (sampling time: 83ms → 50ms)
    • More duration time recording: -0.2~+3s → -1~+30s (panoramic recording)
    • More duration time when power loss: 10s → 60s
    • Accurate time synchronization function: Beidou or GPS
    • Stronger analysis capabilities: real time analysis of voltage drop rate, type of sag, and reasons for sag
    • Solution Recommendation: Based on the analysis results of panoramic recording, recommend the most reasonable solution
    2 Process level (Four major upgrades)
    • Change the touch screen to 10 inches
    • Improve wiring methods: wiring terminals, wiring methods, etc
    • High strength anti vibration structural design
    • Artwork style full art design

    Frequently Asked Questions

    1. What is the primary function of the SAVS recorder?

    The SAVS is a multi-function recorder designed to monitor power systems. It integrates the features of multiple individual instruments to track system stability and power quality on both High Voltage (HV) and Low Voltage (LV) buses.

    2. How does the SAVS monitor and record voltage sags?

    The SAVS provides real-time monitoring and recording of voltage sags. It captures the sag start time (with 1s pre-sag recording), end time (with 30s post-sag recording), duration (identifying down to 1ms sags), drop depth (residual voltage), drop rate, and surge current changes.

    3. Can the SAVS identify the source and phase of a voltage sag?

    Yes. The SAVS features intelligent judgment capabilities to determine if the sag originates from the power grid or a load short circuit. It also discriminates whether the sag affects 1-phase, 2-phases, or 3-phases through phase separation monitoring.

    4. What technical upgrades does the new SAVS feature?

    The SAVS has undergone six major technical upgrades: a higher sampling frequency (up to 20kHz), extended panoramic recording duration (-1s to +30s), extended power loss recording (up to 60s), GPS/Beidou time synchronization, enhanced real-time analysis capabilities, and automatic solution recommendations.

    5. What physical and design improvements have been made to the device?

    The device features four process upgrades: an upgraded 10-inch touch screen interface, improved wiring terminals and methods, a high-strength anti-vibration structural design, and an artwork-style aesthetic layout.

    6. How is the recorded data exported from the SAVS?

    Data can be easily exported directly to a USB flash drive or communicated to the backend system. The device supports multiple communication protocols and interfaces for seamless integration.